RNE CONFIGURATION
VCM-X / RNE Operator Interfaces Technical Guide
30
RNE Con guration Screens
Con guration Screen #5 - Reset Interval Rate
RNE Cnfg ID 101
Reset Interval
Rate...: 20 s
[1-250 Seconds]
If you selected Space or Return Air Temperature Reset in Screen #4,
enter a value in seconds between 1-250. This value determines how fast
the Supply Air Temperature Setpoint is adjusted as the Reset Source
changes. Default is 20 seconds.
Con guration Screen #6 - Dehumidi cation
Control
RNE Cnfg ID 101
Dehumidification
Control: NO
[0=NO 1=YES]
Enter <1> for YES if your system requires Dehumidi cation Control.
Enter <0> for NO. Default is NO.
Con guration Screen #7 - Dehumidi cation
Priority
RNE Cnfg ID 101
Dehumidification
Priority: NO
[0=NO 1=YES]
Enter <1> for YES if Dehumidi cation is a Priority during the Occupied
Mode. Priority means that the Cooling stages will activate based on Coil
Temperature and Reheat will be used regardless of Heating, Cooling, or
Vent Modes of Operation. Enter
<0> for NO.
Con guration Screen #8 - Dehumidi cation
Unoccupied
RNE Cnfg ID 101
Dehumidification
Unoccupied: NO
[0=NO 1=YES]
Enter <1> for YES if Dehumidi cation is required during the Unoccu-
pied mode. Unoccupied Dehumidi cation is activated based on Indoor
Air Humidity only. Enter <0> for NO. Default is NO.
Con guration Screen #9 - Outdoor Humidity
Sensor
RNE Cnfg ID 101
Outdoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is equipped with an Outdoor Air
Humidity Sensor. Enter <0> for NO. Default is NO.
Con guration Screen #10 - Indoor Humidity
Sensor
RNE Cnfg ID 101
Indoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is equipped with an Indoor Air
Humidity Sensor. Enter <0> for NO. Default is NO.
Con guration Screen #11 - Heat During
Dehumidify
RNE Cnfg ID 101
Heat During
Dehumidify: NO
[0=NO 1=YES]
Enter <1> for YES if your application needs to use unit heat during
Dehumidi cation to supplement Reheat. If Reheat is not available, this
selection will allow unit heat to operate in place of Reheat. Enter
<0>
for NO. Default is NO.
Con guration Screen #12 - Economizer
Control
RNE Cnfg ID 101
Economizer
Control: NO
[0=NO 1=YES]
Enter <1> for YES if the RNE is controlling the Economizer. Enter
<0> for NO. Default is NO.
Vedere la pagina 29