VCC-X Controller Technical Guide
VCC-X CONTROLLER WIRING
29
+
-
VCC-X Controller
Remote Supply Air
Temperature Reset Signal
(Configurable 0-10VDC)
(By Others)
NOTE:
Either The Slide Offset Option For The
Space Temperature Sensor May Be Used
Or The Remote Supply Air Temperature
Reset Signal Option (By Others) May Be
Connected To AI6 On The VCC-X
Controller. Only One Option Is Allowed,
Not Both.
AI6
GND
Remote SAT Reset Signal
A Remote Supply Air Temperature Reset Signal can be connected
to AI6 for applications requiring Remote Reset of the Supply Air
Temperature Setpoint. See Figure 15 below.
Remote SAT Reset Wiring
Figure 15: Remote SAT Reset Signal Wiring Diagram