Additional Applications
SA E-BUS Controller Technical Guide
34
Two Condenser Head Pressure Module Overview and Wiring
Two Condenser Head Pressure
Module
The Two Condenser Head Pressure Module ( OE370-23-HP2C)
monitors four individual head pressure transducers and controls two
Condenser Fans or Water Valves on units with two physically separate
condenser sections. The highest reading of head pressure transducers
1 & 2 controls Condenser Signal A. The highest reading of head pres-
sure transducers 3 & 4 controls Condenser Signal B. A pulse width
modulation (PWM) signal is used to control the Condenser Fans. A
0-10 volt output signal is used to control the valves.
Figure 27: Two Condenser Head Pressure Module to E-BUS Distribution Module Wiring Diagram
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
COM
Condenser Fan A
ECM Motor
+
Head Pressure Transducers
0 - 667 PSI
(One Per Refrigerant Circuit)
OE370-23-HP2C
Two Condenser Head Pressure Module
Setting Of OPTIONS
Dip Switch
Not Required When
Used With SA Controller
+5V
SIG 2
GND
OPTIONS
ALARM
ANALOG
STAT
+5V
COMM
GND
SIG 4
GND
BIN 2
R1
R2
GND
RELAYS
ADDRESS
SIG 3
+5V
GND
BIN 1
COM
+5V
SIG 1
R3
R4
Rc
AO1
AO2
PWM1-
PWM1+
PWM2-
PWM2+
This Dip Switch Is Not
Used For This Application
PWR
COM
Condenser Fan B
ECM Motor
+
COM
COM
+
+
VFD Condenser A Signal
For Air Cooled
Condenser Applications
VFD Condenser B Signal
For Air Cooled
Condenser Applications
Head Pressure Control
Valve Actuator - A
For Water Cooled
Condenser Applications
Head Pressure Control
Valve Actuator - B
For Water Cooled
Condenser Applications
Connect To The
SA E-BUS Controller
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
HSSC Cable
24 VAC Transformer
3 VA Minimum
Line Voltage
24 VAC
GND
WARNING!!
Observe Polarity! All
Boards Must Be Wired
With GND-to-GND And
24 VAC-To-24 VAC.
Failure To Observe
Polarity Could Result In
Damage To The Boards.
HSSC Cable
Use For Dual
Applications Only
Use For
Dual
Applications
Only
Use For
Dual
Applications
Only
3 (Y)
3 (Y)
5 (U)
5 (U)
2 (+)
2 (+)
1 (-)
1 (-)
1 (-)
1 (-)
The Two Condenser Head Pressure Module connects to the SA E-
BUS Controller, allowing the Two Condenser Head Pressure Module
to receive setpoints from the SA E-BUS Controller. See Figure 27
below for wiring diagram.
The Two Condenser Head Pressure Module requires a 24 VAC power
connection with an appropriate VA rating.
NOTE: For complete information, including the sequence of
operation, refer to the Two Condenser Head Pressure Module
Technical Guide.