HB Controller Technical Guide
Condenser Fan Control Setpoints
Description Min. Default Max.
Liquid Line Cut Out Temperature 75ºF 85ºF 95ºF
Liquid Line Cut In Temperature 95ºF 105ºF 115ºF
Table 12: Condenser Fan Control Setpoints
Miscellaneous Control Setpoints
Description Min. Default Max.
Force Mode Timer 1 Min 60 Min 240 Min
Table 13: Miscellaneous Control Setpoints