Orion-system E-BUS Distribution Manuale Utente Pagina 8

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 7
E-BUS Distribution Module
Technical Guide
8
Installation and Wiring
Figure 6: Air ow Monitoring Station To E-BUS Wiring
NOTE: This option is not available for the SA Controller.
Air Flow Monitoring Station
Installation and Wiring
The E-BUS Distribution Module is used to connect selected Air Flow
Monitoring Stations to the VCM-X Controller. Currently, there are two
Air Flow Monitoring Station options that are supported in our standard
software.
• EBTRON
®
- GTC-116 Series Air Flow Monitoring Station*
GreenTrol™ Automation - GA-200-N Module used with
any GF Series Air Flow Monitoring Station
*NOTE: When con guring the GTC-116 Series, be sure to set
the Parity to “NO PARITY, 1 STOP BIT.”
The Paragon MicroTrans EQ series Air Flow Monitoring Station is
supported only on the VCM-X Controller using custom software.
Contact the WattMaster factory for more information. The wiring for
these options are the same and are shown in Figure 6.
The E-BUS Distribution Module provides a communications interface
into the VCM-X Controller to enable it to monitor and display the
air ow readings of these air ow stations.
NOTE: Only one E-BUS Distribution Module can be used per
control system.
24 VAC Transformer
Line Voltage
24 VAC
GND
WARNING!!
Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
To observe polarity could result in
damage to the boards.
E-BUS Distribution Module
Modular Cable
Connect to Either VCM-X Controller,
or 12 Relay Expansion Module
COMM
COMM
COMM
NET-
NET-
NET-
NET+
NET+
NET+
Airflow Measurement
Digital Transmitter Terminals
For Outdoor Air CFM
(Set Address Switch To 9)
Airflow Measurement
Digital Transmitter Terminals
For Return Air CFM
(Set Address Switch To 10)
Airflow Measurement
Digital Transmitter Terminals
For Supply Air CFM
(Set Address Switch To 11)
TB5
SERIAL #
U2
C9
R22R21R20
C8
J3
J4
J5
R4
R5
.1uF
4751
485 DRV
1001 1000 1001
24VAC
GND
PWR
4751
YS102308
REV 3
I2C TO COMM
DIST. BOARD
.01uF
GND
-COMM
SHLD
+COMM
INPUT
+COMM
SHLD
-COMM
GND
+VDC
OUTPUT
TB2
TB1
R17
R18
R19
HB
I2C
SIO
OUTPUTOUTPUT OUTPUT OUTPUT
+COMM
+COMM
+24 VAC
SHLD
SHLD
GND
-COMM
-COMM
GND
GND
+VDC
OE365-23-EBD E-BUS DISTRIBUTION MODULE
WattMaster Label
#LB102058
Rev.: 1C
E-BUS
INPUT CONN.
I2C
CONNECTOR
I2C
CONNECTOR
www.orioncontrols.com
E-BUS
OUTPUT
E-BUS
OUTPUT
E-BUS
OUTPUT
E-BUS
OUTPUT
E-BUS
OUTPUT
E-BUS
INPUT
POWER
VCM-X WSHP Controller, VCM-X Expansion Module,
VCM-X Modular Controller,
Vedere la pagina 7
1 2 3 4 5 6 7 8 9 10 11 12

Commenti su questo manuale

Nessun commento